18 Aug 2025 OWASA Updates Cross-Connection Control Requirements
OWASA has recently updated its requirements related to cross-connection control and backflow protection. In January 2025, the OWASA Manual of Standards, Specifications and Design; in November 2024 and August 2025, the OWASA Cross-Connection Control Manual; and in August 2025, the OWASA Ordinance for the Control of Backflow and Cross-Connections, were revised. The overall review of cross-connection control requirements was precipitated by changes to North Carolina State Statutes under Session Law 2024-49.
The fundamental requirement for applicability of backflow protection for new service connections has not changed:
- All new service lines, with the exception of a domestic service to a single-family residence with no swimming pool, hot tub, spa, in-ground irrigation system, fire suppression, auxiliary water supply, or other OWASA-identified hazard, will be required to have backflow protection.
- All newly installed backflows must be high-hazard testable assemblies: Reduced Pressure Principle or Reduced Pressure Principle Detector Assemblies. Double Check Detector Assemblies can be repaired but not replaced.
Some specific provisions for new services and the applicability of requirements to existing services have been updated. Key changes are as follows:
- Existing services with no known high hazard will not be required to add backflow protection during remodeling or plumbing upfit of an existing building unless the facility is on the published North Carolina Department of Environmental Quality’s list of High Hazard Service Connections, or the backflow is required by the NC Plumbing Code or NC Building Code.
- All new irrigation systems shall have a dedicated water service and meter consistent with North Carolina State requirements for drought preparedness and response. This requirement will be effective for permits initiated after October 1, 2025.
- For single-family residential installations, location of backflow assembly after a tee may be granted if the tee leads to the service line branch solely serving the identified hazard.
- Backflow piping material requirement on the customer side of the water meter now defers to the NC Plumbing Code.
- A service valve shall be installed after the meter and prior to every containment assembly to allow testing, maintenance, and replacement of the backflow assembly without the use of an OWASA operating valve.
- Backflow assemblies for domestic purposes only that are two inches or smaller do not require heat within the protective housing. For residential irrigation systems and pools, protective enclosures for freeze protection are not required if the backflow assembly is installed with unions and an upstream shutoff and is removeable for winterization.
- Backflows that remain in service year-around for irrigation systems with no chemical feeds or booter pumps may be tested once every three years instead of annually. Annual certification that no chemical feed is present is required. If the backflow is removed for winterization, testing within 10 days of reinstallation is required.
Please contact Zac Eitel at 919-537-4375 or zeitel@owasa.org with any questions.